Voltage Drop & Wire Gauge (AWG) Calculator

Calculate voltage drop over a copper or aluminum cable run by AWG size, current and length — and find the smallest wire gauge that keeps the drop under 3%.

How to use

  1. 1Enter the voltage, current, one-way length and wire material.
  2. 2Pick a gauge to check, or read the suggested gauge for a 3% drop.

How it's calculated

Resistance = ρ × length ÷ area. Voltage drop = 2 × I × R_one-way for single-phase/DC (√3 × I × R for three-phase). AWG diameter = 0.127 mm × 92^((36 − n) ÷ 39).

Frequently asked questions

What voltage drop is acceptable?

The NEC recommends (in an informational note) no more than 3% on a branch circuit and 5% overall.

Is voltage drop the same as ampacity?

No — ampacity is how much current a wire can safely carry without overheating. Check both; the minimum ampacity column shows NEC 75 °C copper ratings.

Should I trust this for electrical work?

Use it for planning. Wiring must follow your local electrical code, and a licensed electrician should verify permanent installations.

Sources

A worked example: 15 A, 100 feet, 12 AWG copper

100 feet one-way is 30.48 m. 12 AWG copper has a cross-section of about 3.31 mm², and copper's resistivity is 1.724×10⁻⁸ Ω·m. Because current has to travel out and back through a single-phase/DC circuit, the formula doubles the one-way length: drop = 2 × 15 A × 1.724×10⁻⁸ × 30.48 ÷ (3.31×10⁻⁶) ≈ 4.8 V, which is 4%, slightly over the 3% guideline — matching the tool's own example. Stepping up to 10 AWG (area ≈ 5.26 mm²) drops that to about 3.0 V, or 2.5% — under the guideline, which is why the tool suggests 10 AWG as the smallest gauge that clears 3% for this exact run.

Why the length gets doubled — and why three-phase uses √3 instead

A single-phase or DC circuit's current flows down one conductor and back through another (or a shared neutral), so the resistance that actually causes voltage drop is twice the one-way run's resistance — that's the ×2 in the formula. Three-phase systems don't double the same way: because the three phases are 120° apart, the drop formula uses a factor of √3 instead, reflecting the line-to-line voltage relationship rather than a simple there-and-back path.

Why the AWG numbers run backward, and two separate limits to check

Wire gauge numbers get smaller as the wire gets physically bigger, because the American Wire Gauge system is defined by diameter = 0.127 mm × 92^((36 − gauge) ÷ 39) — every 3 steps down in gauge number roughly doubles the cross-sectional area, a relic of the wire-drawing dies the standard was built around. Voltage drop and ampacity are two independent checks: this tool's ampacity column comes from NEC Table 310.16's 75°C copper column, further capped for 14/12/10 AWG by NEC 240.4(D)'s small-conductor overcurrent limits (15/20/30 A) — so a wire can pass the 3% drop guideline and still be undersized for the breaker, or vice versa, and both need to check out.

The suggested gauge is the thinnest wire that still passes

The suggestion walks from the thinnest listed gauge toward the thickest and stops at the first one whose drop is 3 percent or less, so I am offered the smallest copper or aluminum that meets the guideline, not a heavier wire than I need. If even 4/0 is over 3 percent, the line says to use parallel runs. Ampacity is shown only for copper, and for 14, 12, and 10 AWG it is capped at 15, 20, and 30 amps by the small-conductor rule, which is why 12 AWG reports 20 amps here even though the 75 °C table allows 25. If my current is above that cap I get a note that the current exceeds the wire's rating, separate from the drop hint.