Watts, Volts & Amps Calculator (DC, AC, 3-Phase)
Convert between watts, amps and volts for DC, single-phase AC and three-phase circuits, including power factor.
How to use
- 1Choose DC, single-phase or three-phase.
- 2Enter two of watts, volts and amps (and the power factor for AC motors).
How it's calculated
DC: P = V × I. Single-phase AC: P = V × I × PF. Three-phase: P = √3 × V(line-to-line) × I × PF.
Frequently asked questions
How many amps is a 1,500 W heater on 120 V?
1,500 ÷ 120 = 12.5 A — too much for a 15 A circuit shared with other loads.
What is power factor?
The ratio of real power to apparent power. Resistive loads (heaters) are 1.0; motors are often 0.8–0.9.
What's the difference between kW and kVA?
kW is real power; kVA is apparent power (V × I). kW = kVA × power factor.
A worked example: a three-phase motor
A three-phase load at 400 V (line-to-line), 10 A and power factor 0.85 computes real power as P = √3 × 400 × 10 × 0.85 ≈ 5,889 W — the tool's own built-in example. Dividing by the power factor gives the apparent power, about 6,929 VA: the extra ~1,040 VA is power the supply still has to carry (in current and wiring capacity) even though it isn't doing useful work, which is exactly what power factor measures.
Why three-phase gets a √3, not a simple ×3
It's tempting to assume three wires means three times the power of one, but the three phases are offset by 120° from each other, not aligned — the √3 factor (≈1.732) comes directly from that phase geometry relating line-to-line voltage to the per-phase quantities, not from literally tripling anything. That's also why three-phase motors draw noticeably less current than three separate single-phase circuits would for the same delivered power.
Why DC never needs a power factor
Power factor only exists because AC voltage and current are sine waves that can drift out of phase with each other when a load has reactance (a motor's windings, a switching power supply) — multiplying their peak or RMS values alone overstates the real power delivered, so power factor corrects for the mismatch. DC has no frequency and no phase angle to drift, so voltage and current are always simply multiplied; that's why this tool hides the power factor field entirely in DC mode rather than fixing it at 1.
It opens on a 1,500 watt heater
The form starts on single-phase AC with 1,500 watts and 120 volts filled in and the amps box empty, so the first answer is 12.5 amps at a power factor of 1. That unknown amps figure is the one marked as the result I asked for; if I clear watts instead and type the current, power becomes the highlighted answer. I have to leave exactly one of watts, volts, and amps empty. Filling all three, or only one, stops the calculation. On three-phase the same rule holds, but the power uses line-to-line volts times current times the square root of 3 times the power factor, which is why 400 volts, 10 amps, and a power factor of 0.85 comes out near 5,889 watts.
A blank or zero power factor is treated as 1
Power factor only appears for AC. If I wipe that box, or type 0, the tool does not refuse the sum. It treats the factor as 1, the same as a heater or any purely resistive load, and carries on. Apparent power, in volt-amps, is the real watts divided by that factor, so a 0.85 motor shows more VA than watts. On DC the power-factor box is hidden entirely and apparent power is not listed, because there is no phase angle to correct for. I check which system is selected before I trust a per-mile or per-circuit current, since the same watts and volts give a different current once three-phase or a power factor below 1 is involved.
Related tools
- Ohm's Law Calculator
Enter any two of voltage, current, resistance and power to calculate the other two with Ohm's law and the power formulas.
- Moon Phase Calculator
Find the moon phase, illumination and moon age for any date — plus the dates of the next new moon and full moon.
- Air Conditioner Size (BTU) & Heating Calculator
Find the right air conditioner size in BTU for a room using the ENERGY STAR chart, with adjustments for sun, occupants and kitchens — plus a heating BTU estimate by climate.
- Voltage Drop & Wire Gauge (AWG) Calculator
Calculate voltage drop over a copper or aluminum cable run by AWG size, current and length — and find the smallest wire gauge that keeps the drop under 3%.
- Power Converter (kW ↔ HP)
Convert watts, kilowatts, horsepower (mechanical and metric), BTU per hour and refrigeration tons.
- Plug Type & Voltage by Country
Which power plug and voltage each country uses — so you know whether you need a travel adapter, a voltage converter, or neither.